Products | Binary industrial sensors InBin.. Schischek GmbH ExplosionproofEx..Red..In..

Binary sensors for safe area
Protection class IP66 | not Explosion proof

InBin-P pressure/differential pressure switch (pressostat)

Binary pressure/diff. pressure switch (Pressostat) ΔP

Measurements ..Bin-P Sensor: L × B × H = 177 × 107 × 66 mm

Measurements in mm

Description – Binary differential pressure switch (Pressostat) InBin-P..

  • Pressure switches for HVAC systems, e.g. for differential pressure control for filter- or fan belt monitoring
  • No additional module in the panel required!
  • No intrinsically safe wiring required!
  • All parameters adjustable on site w/o additional tools/meas. devices

InBin-P..

0 - 500 Pa, 0 - 5.000 Pa1-channel or 2-channel adjustable5.000 Pa - 50.000 Pa24 VAC / DCPotential free switching contact adjustable per menuLCD Backlit, defeatable
Switching status LEDs
IP 66 / Aluminium casting, coated-20°...+50°C, 0...95 %rHintegrated terminal boxca. 950 gsafe area

Delivery – InBin-P..

  • Pressure switch with integrated terminal box
  • 3 × Tapping screw Ø 4,2 × 13 mm
  • 1 × Short circuit tube ca. 140 mm length

Special models – InBin-P... - 2

  • Pressure switch with two switching outputs (2 × potential free contacts)

Accessories – InBin-P..

  • „Installation kit 2“ includes 2 m pressure hose Ø 6 mm inner diameter,
    2 plastic fittings
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
InBin-FR frost protection thermostat – binary, activ

Frost protection thermostat – binary, activ°C

Measurements ..Bin-FR Sensor: L × B × H = 177 × 107 × 66 mm

Measurements in mm

Description – Frost protection thermostat InBin-FR..

  • Frost protection thermostats for HVAC systems, e.g. frost protection monitoring of heating registers / heat exchangers
  • No additional module in the panel required!
  • No intrinsically safe wiring required!
  • Switch-point mechanically adjustable

InBin-FR..

-10 °C...+15 °C1-stage (1-channel)3 meters or 6 meters24 VAC / DC~ 40 cm1 potential-free contactSwitching status with LEDsIP 66 / Aluminium casting, coated-20°...+50°C, 0...95 %rHintegrated terminal boxca. 950 gsafe area

Delivery – InBin-FR..

  • Frost protection thermostat with integrated terminal box and 3 m
    or 6 m capillary (dependent by Type)
  • 3 × Tapping screw Ø 4,2 × 13 mm

Accessories – InBin-FR..

  • „Installation kit 1.3“: Cappillary duct, assembly cramp and 4 assembly brackets (for InBin-FR3)
  • „Installation kit 1.6“: Cappillary duct, assembly cramp and 8 assembly brackets (for InBin-FR6)
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
InBin-N Fan belt monitoring via speed control

Fan belt monitoring, binary Umin
via contactless speed control

Measurements ..Bin-N Sensor: L × B × H = 177 × 107 × 66 mm

Measurements in mm

Description – Fan belt guard via speed control InBin-N..

  • Fan belt monitoring modul (V-belt guard) for HVAC systems, via speed control of fan drive shaft
  • No additional module in the panel required!
  • No intrinsically safe wiring required!
  • Switch-point in min¹ is digitally adjustable
  • Integrated, adjustable time switch relais

InBin-N..

0 - 10.000 min¹1-stage or 2-stage, 50 - 10.000 min¹24 VAC / DCNamur transducer inductive, DIN 19234Potential free switching contact adjustable per menuLCD Backlit, defeatable
Switching status LEDs
IP 66 / Aluminium casting, coated-20°...+50°C, 0...95 %rHintegrated terminal boxca. 950 gsafe area

Delivery – InBin-N..

  • Fan belt monitoring modul with integrated terminal box and directly mountable Namur transducer
  • 3 × Tapping screw Ø 4,2 × 13 mm

Special models – InBin-N-2

  • Version with 2-stage switch point (2 × potential-free contacts)

Accessories – InBin-N..

  • „Installation kit 3“: Mountingset for Namur transducer onto ventilators /
    propellers up to approx. 20.000 m³/h (Empirical values – they can vary depending on the construction of ventilator / propeller)
  • „Installation kit 4“: Mountingset for Namur transducer onto ventilators /
    propellers over approx. 20.000 m³/h (Empirical values...)
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
InBin-D Thermostat / Hygrostat, binary

Thermostat / Hygrostat – binary°C %rH

Description – Thermostat / Hygrostat InBin-D..

  • Use together with InPro-B.. sensor probe as thermostat or hygrostat in HVAC systems
  • No additional module in the panel required!
  • No intrinsically safe wiring required!
  • Selectable on site if used for room or duct application!
  • Switch-point for °C and %rH is separately adjustable (dependent on sensor probe type)
  • Adjustable directly on site without additional tools / meas. devices

InBin-D..

-40 °C...+125 °C0...100 %rHRoom- and / or Duct-measurement24 VAC / DC1 × InPro-B.. sensor probePotential free switching contact adjustable per menuLCD Backlit, defeatable
Switching status LEDs
IP 66 / Aluminium casting, coated-20°...+50°C, 0...95 %rHintegrated terminal boxca. 950 gsafe area

Delivery – InBin-D..

  • Module with integrated terminal box and socket for one InPro-B..
    sensor probe
  • 3 × Tapping screw Ø 4,2 × 13 mm
  • Required accessory: InPro-B.. sensor probe

Special models – InBin-D-2

  • Module with 4-stage output (4 pot.-free contacts = 2 × °C, 2 × %rH)

Accessories – InBin-D..

InPro-B.. digital sensor probes, suitable for InBin-D Thermostat/Hygrostat
InBin-A Switching module, binary

Switching modules – binary°C %rH ΔP

Measurements ..Bin-A Sensor: L × B × H = 177 × 107 × 66 mm

Measurements in mm

Description – Switching module InBin-A..

  • Switching modules for direct mounting in safe area
  • Use in HVAC systems (Heating, Ventilating and Air Conditioning)
  • Connection of 1, 2 or 5 passive, potential-free binary sensors
  • No additional module in the panel required!
  • No intrinsically safe wiring required!

InBin-A..

24 VAC / DCThermostats TBR-2.., TBK.., TBT..
Humiditystats FBR-2G.., FBK-2G..
Diff. pressure switch DBK..,
Air flow switch WFBK-2G..
Frost protection thermostat TBK-FR-2G..
Potential-free switching contactActual value indication LEDsIP 66 / Aluminium casting, coated-20°...+50°C, 0...95 %rHintegrated terminal boxca. 950 gsafe area

Delivery – InBin-A..

  • Switching module with socket for 1, 2 or 5 binary passive sensors
    (dependent on type)
  • 3 × Tapping screw Ø 4,2 × 13 mm
  • Optional accessory: Binary passive sensors

Accessories – InBin-A..

  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
back to Product choice

Products for
zone 1, 2, 21, 22
(Example ExMax)

Products for
zone 2, 22
(Example RedMax)

Products for
safe area
(Example InMax)

 
 
 
 
Actuators and sensors for ship building, offshore, onshore, FPSO Actuators and sensors for HVAC systems (heating, ventilation, airconditioning), climate control Actuators and sensors for chemistry, pharmacy, industry Actuators and sensors for power plants, water treatment, landfills Schischek contact worldwide Schischek GmbH Explosionproof – Home Schischek GmbH Explosionproof – Home