Products | Sensors InCos.. 
Sensors for safe area (industrial application) Protection class IP66 | not Explosion proof
Differential pressure-/VAV-Sensors ΔP
Technical dataMeasurement range*Min. range*Overload protected*Electric supplyOutputDisplayHousing protectionAmbient temperature/-humidityPower supplyWeightInstallation area Modul*dependent by Type
InCos-P± 100 Pa - ± 7.500 Pa20 Pa25.000 Pa - 120.000 Pa24 VAC / DC0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)safe area
Delivery – InCos-P..
- 1 × Sensor InCos-P with integrated terminal box
- 3 × Tapping screw Ø 4,2 × 13 mm
- 1 × Short circuit tube ca. 140 mm length
Special models – InCos-P..-A
- Modul with one 4..20 mA output to connect external actual value indicator
Accessories – InCos-P..
- External LCD indicator connectable to InCos-P..-A sensors,
mounting in safe area
- Mounting-bracket for installation on round air-ducts up to Ø 600 mm
- „Installation kit 2“ includes 2 m pressure hose Ø 6 mm inner diameter,
2 plastic fittings
Temperature-/humidity transducer°C,%rH Combination with InPro-C.. digital sensors
Technical dataMeasurement range Temperature*Measurement range Humidity*ApplicationElectric supplyConnectable sensorsOutputDisplayHousing protectionAmbient temperature/-humidityPower supplyWeightInstallation area Modul*dependent by sensor InPro-C..
InCos-D-40 °C...+125 °C0...100 %rHRoom- and / or Duct-measurement24 VAC / DC1 × InPro-C.. Sensor0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)safe area
Delivery – InCos-D..
- 1 × Module InCos-D with integrated terminal box
- 3 × Tapping screw Ø 4,2 × 13 mm
- Required accessory: InPro-C.. Sensor
Special models – InCos-D-A
- Modul with two 4..20 mA outputs to connect external actual value
indicator (Output 1 for °C, Output 2 for %rH)
Accessories – InCos-D..
- InPro-C.. digital sensors
- External LCD indicator connectable to InCos-DA transducer,
mounting in safe area
- Mounting-bracket for installation on round air-ducts up to Ø 600 mm
Temperature-/humidity transducer°C, %rH Combination with passive sensors
Technical dataElectric supplyConnectable sensors (passive sensors) OutputDisplayHousing protectionAmbient temperature/-humidityPower supplyWeightInstallation area Modul
InCos-A24 VAC / DCmodulating, passive, potential free: Pt 100, Pt 500, Pt 1000, Ni 100, Ni 200, Ni 500, Ni 1000, Ni 1000 Siemens, KP 250, Resistance output 0...1 kOhm, 0...10 kOhm0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)safe area
Delivery – InCos-A..
- 1 × Sensor InCos-A with integrated terminal box
- 3 × Tapping screw Ø 4,2 × 13 mm
- Required accessory: passive sensor
Special models – InCos-A-A
- Modul with one additional 4..20 mA output to connect a external actual value indicator
Accessories – InCos-A..
- External LCD indicator connectable to InCos-AA transducer,
mounting in safe area
- Mounting-bracket for installation on round air-ducts up to Ø 600 mm
|
Products for zone 1, 2, 21, 22 (Example ExMax)
Products for zone 2, 22 (Example RedMax)
Products for safe area (Example InMax)
|