ATEX 94/9/EC | zone 1, 2, 21, 22

ExCos-P Differential pressure-/VAV-sensors

Differential pressure-/VAV-Sensors ΔP

Measurements ..Cos-P Sensor: L × W × H = 177 × 107 × 66 mm

Measurements in mm

ExCos-P

± 100 Pa - ± 7.500 Pa20 Pa25.000 Pa - 120.000 Pa24 VAC / DC0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)gases, mists, vapours, dustzone 1, 2, 21, 22II2(1)G Ex ema [ia] IIC T6II2(1)D Ex tD A21 [iaD] IP66 T80°C

Delivery – ExCos-P..

  • 1 × Sensor ExCos-P with integrated Ex-e terminal box
  • 3 × Tapping screw Ø 4,2 × 13 mm
  • 1 × Short circuit tube ca. 140 mm length

Special models – ExCos-P..-A

  • Modul with one intrinsically 4..20 mA output to connect external actual value indicator

Accessories – ExCos-P..

  • Intrinsic, external LCD indicator connectable to ExCos-P..-A sensors, mounting in hazardous areas zone 1, 2, 21, 22
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
  • „Installation kit 2“ includes 2 m pressure hose Ø 6 mm inner diameter,
    2 plastic fittings

to the technical data sheetsto the technical data sheets

ExCos-D Temperature-/humidity transducer

Temperature-/humidity transducer°C,%rH
Combination with ExPro digital sensors

Measurements ..Cos-D Sensor: L × W × H = 177 × 107 × 66 mm

Measurements in mm

ExCos-D

-40 °C...+125 °C0...100 %rHRoom- and / or Duct-measurement24 VAC / DC1 × ExPro Sensor0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)gases, mists, vapours, dustzone 1, 2, 21, 22II2(1)G Ex ema [ia] IIC T6II2(1)D Ex tD A21 [iaD] IP66 T80°C

Delivery – ExCos-D..

  • 1 × Sensor ExCos-D with integrated Ex-e terminal box
  • 3 × Tapping screw Ø 4,2 × 13 mm
  • Required accessory: ExPro Sensor

Special models – ExCos-D-A

  • Modul with two intrinsic 4..20 mA outputs to connect Ex-i external
    actual value indicator (Output 1 for °C, Output 2 for %rH)

Accessories – ExCos-D..

  • ExPro digital sensors
  • Intrinsic, external LCD indicator connectable to ExCos-DA transducer, mounting in hazardous areas zone 1, 2, 21, 22
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm
ExPro digital sensors, compatible for ExCos-D / RedCos-D transducer

to the technical data sheetsto the technical data sheets

ExCos-A Temperature-/humidity transducer

Temperature-/humidity transducer°C,%rH
Combination with passive sensors

ExCos-A

24 VAC / DCmodulating, passive, potential free, Type ExSens:
Pt 100, Pt 500, Pt 1000, Ni 100, Ni 200,
Ni 500, Ni 1000, Ni 1000 Siemens, KP 250, Resistance output 0...1 kOhm, 0...10 kOhm
0-10 V DC, (0)4-20 mA, selectable on siteBacklit, defeatableIP 66-20°...+50°C, 0...95 %rHover integrated terminal boxca. 950 g (Aluminium housing)gases, mists, vapours, dustzone 1, 2, 21, 22II2(1)G Ex ema [ia] IIC T6II2(1)D Ex tD A21 [iaD] IP66 T80°C

Delivery – ExCos-A..

Special models – ExCos-A-A

  • Modul with one additional intrinsically 4..20 mA output to connect a
    Ex-i external actual value indicator

Accessories – ExCos-A..

  • Intrinsic, external LCD indicator connectable to ExCos-AA transducer, mounting in hazardous areas zone 1, 2, 21, 22
  • Mounting-bracket for installation on round air-ducts up to Ø 600 mm

to the technical data sheetsto the technical data sheets

back to Product choice

Products for
zone 1, 2, 21, 22
(Example ExMax)

Products for
zone 2, 22
(Example RedMax)

Products for
safe area
(Example InMax)

      