Max-5.10-SF, Max-5.10-SF-CTS, Max-5.10-SF-VAS

Mechanical properties

min.

typ.

max.

unit

Motor torque (can be configured with rotary switch)*

5 / 10

Nm

Motor runtime for 90° (can be configured with rotary switch)*

3
15
30
60
120

s

Spring torque*

10

Nm

Spring return time for 90° (can be configured with wire bridge on connection)*

3 / 10

s

Minimum angle of rotation*

-5

°

Maximum angle of rotation*

90

°

Weight*

  • Max-5.10-SF
  • Max-5.10-SF-CTS
  • Max-5.10-SF-VAS

 

3.8

3.8

5.6

 

kg

kg

kg

Dimensions

min.

typ.

max.

unit

Max-5.10-SF

L
W
H

 

–1
–1
–1

 

210
96
80

 

+1
+1
+1

 

mm
mm
mm

Max-5.10-SF-CTS

L
W
H

 

–1
–1
–1

 

210
96
80

 

+1
+1
+1

 

mm
mm
mm

Max-5.10-SF-VAS

L
W
H

 

–1
–1
–1

 

211
96
81

 

+1
+1
+1

 

mm
mm
mm

Hollow shaft double square

12 x 12

mm

Allen key provided for manual adjustment in accordance with these instructions*

3

mm

Electrical characteristics

min.

typ.

max.

unit

Minimum nominal voltage (at room temperature)

–10 %

24

+10 %

VAC/DC

Maximum nominal voltage (at room temperature)

–10 %

240

+10 %

VAC/DC

Minimum mains frequency

–20 %

50

+20 %

Hz

Maximum mains frequency

-20 %

60

+20 %

Hz

Nominal current (at room temperature)

Power consumption as a function of supply voltage

Power consumption standby*

5

W

Power consumption heating mode*

16

W

Power consumption in operation

Power consumption as a function of supply voltage

Switch-on peak

  • at 24 VDC (for approx. 2 seconds)*
  • at 240 VDC (for approx. 2 seconds)*

 

2

2

 

A

A

Maximum duty cycle for motor run time*

3 s


15 s, 30 s, 60 s, 120 s

 

60 s enforced pause after 3 s motor operation

100

 

 


%

Electrical connection options

3-point with spring return with configurable spring return period

Cable type 5+PE, cable diameter 7.5 mm

1-wire with spring return with configurable spring return period

Cable type 5+PE, cable diameter 7.5 mm

Integrated limit switch

Cable type 6, cable diameter 7.4 mm

Electrical characteristics limit switch

min.

typ.

max.

unit

Switch point CLOSED

Switch point OPEN

-2

-2

5

85

+2

+2

°

°

Signal operation

  • Umax DC*
  • Imax DC*
  • Imin AC/DC*

 

48

1

5

 

V

A

mA

Power operation

  • Umax AC*
  • Umin AC/DC*
  • Imax AC*

 

250

5

5

 

V

V

A

After one-off operation
with U > 24 VAC/DC or I > 100 mA:

  • Umin AC/DC*
  • Imin AC/DC*


12

100


V

mA

Environmental conditions

min.

typ.

max.

unit

Humidity (not condensing)

90

% rH

Protection class as per DIN EN 60529

IP66

Operation

  • Ambient temperature (T6)
  • Ambient temperature (T5)

–40

–40

+40

+50

°C

°C

Storage

  • Ambient temperature

–40

+70

°C

*: Nominal value: please note that nominal values are also subject to tolerances. For more detailed information, see: Note on nominal values