Max-5.10-CY, Max-5.10-CY-CTS, Max-5.10-CY-VAS
Mechanical properties | min. | typ. | max. | unit |
---|---|---|---|---|
Motor torque (can be configured with rotary switch)* | 5 / 10 | Nm | ||
Motor runtime for 90° (can be configured with rotary switch)* | 7.5 | s | ||
Minimum angle of rotation* | -5 | ° | ||
Maximum angle of rotation* | 90 | ° | ||
Weight*
|
3.5 3.5 5.3 |
kg kg kg |
Dimensions | min. | typ. | max. | unit |
---|---|---|---|---|
Max-5.10-CY L |
–1 |
210 |
+1 |
mm |
Max-5.10-CY-CTS L |
–1 |
210 |
+1 |
mm |
Max-5.10-CY-VAS L |
–1 |
211 |
+1 |
mm |
Hollow shaft double square | 12 x 12 | mm | ||
Allen key provided for manual adjustment in accordance with these instructions* | 3 | mm |
Electrical characteristics | min. | typ. | max. | unit |
---|---|---|---|---|
Minimum nominal voltage (at room temperature) | –10 % | 24 | +10 % | VAC/DC |
Maximum nominal voltage (at room temperature) | –10 % | 240 | +10 % | VAC/DC |
Minimum mains frequency | –20 % | 50 | +20 % | Hz |
Maximum mains frequency | –20 % | 60 | +20 % | Hz |
Power consumption standby* | 5 | W | ||
Power consumption heating mode* | 16 | W | ||
Power consumption in operation | ||||
Switch-on peak
|
2 2 |
A A | ||
Maximum duty cycle for motor run time 7.5 s, 15 s, 30 s, 60 s, 120 s |
100 |
% |
Electrical connection options | |
---|---|
Cable type 5+PE, cable diameter 7.5 mm |
Activation CY-drives | min. | typ. | max. | unit |
---|---|---|---|---|
Power supply / frequency | ||||
Minimum voltage | –10 % | 24 | +10 % | VAC/DC |
Maximum voltage | –10 % | 240 | +10 % | VAC/DC |
Minimum frequency | –20 % | 50 | +20 % | Hz |
Maximum frequency | –20 % | 60 | +20 % | Hz |
Activation Y | 4 | 20 | mA | |
Feedback signal U | 0 | 10 | VDC | |
Performance data Y and U
|
0 0 |
|
10 10 |
VDC VDC |
Environmental conditions | min. | typ. | max. | unit |
---|---|---|---|---|
Humidity (not condensing) | 90 | % rH | ||
Protection class as per DIN EN 60529 | IP66 | |||
Operation | ||||
| –40 –40 | +40 +50 | °C °C | |
Storage | ||||
| –40 | +70 | °C |
*: Nominal value: please note that nominal values are also subject to tolerances. For more detailed information, see: Note on nominal values