Max-8-F1, Max-8-F1-CTS, Max-8-F1-VAS
Mechanical properties | min. | typ. | max. | unit |
---|---|---|---|---|
Motor torque* | 8 | Nm | ||
Motor runtime for 90° (can be configured with rotary switch)* | 3 | s | ||
Spring torque* | 6 | Nm | ||
Spring return time for 90° (can be configured with rotary switch) | ~1 | s | ||
Load torque, value must not be below this | 2 | Nm | ||
Minimum angle of rotation* | -5 | ° | ||
Maximum angle of rotation* | 90 | ° | ||
Weight*
|
4.0 4.0 5.6 |
kg kg kg |
Dimensions | min. | typ. | max. | unit |
---|---|---|---|---|
Max-8-F1 L |
–1 |
210 |
+1 |
mm |
Max-8-F-CTS L |
–1 |
210 |
+1 |
mm |
Max-8-F1-VAS L |
–1 |
211 |
+1 |
mm |
Hollow shaft double square | 12 x 12 | mm | ||
Allen key provided for manual adjustment in accordance with these instructions* | 3 | mm |
Electrical characteristics | min. | typ. | max. | unit |
---|---|---|---|---|
Minimum nominal voltage (at room temperature) | –10 % | 24 | +10 % | VAC/DC |
Maximum nominal voltage (at room temperature) | –10 % | 240 | +10 % | VAC/DC |
Minimum mains frequency | –20 % | 50 | +20 % | Hz |
Maximum mains frequency | -20 % | 60 | +20 % | Hz |
Nominal current (at room temperature) | ||||
Power consumption standby* | 5 | W | ||
Power consumption heating mode* | 16 | W | ||
Power consumption in operation | ||||
Switch-on peak
|
2 2 |
A A | ||
Maximum duty cycle for motor run time* 3 s
|
60 s enforced pause after 3 s motor operation 100 |
|
Electrical connection options | |
---|---|
Cable type 3+PE, cable diameter 6.0 mm | |
Cable type 3+PE, cable diameter 6.0 mm |
Ambient conditions | min. | typ. | max. | unit |
---|---|---|---|---|
Humidity (non-condensing) | 90 | % rH | ||
Degree of protection to EN 60529 | IP66 | |||
Operation | ||||
| -20 -20 | +40 +50 | °C °C | |
Storage | ||||
| -40 | +70 | °C |
*: Nominal value: please note that nominal values are also subject to tolerances. For more detailed information, see: Note on nominal values