Max-50.75-Y, Max-50.75-Y-CTM
Mechanical properties | min. | typ. | max. | unit |
---|---|---|---|---|
Motor torque (can be configured with rotary switch)* |
| 50/75 |
| Nm |
Motor runtime for 90° (can be configured with rotary switch)* |
| 40 |
| s |
Minimum angle of rotation* |
| -5 |
| ° |
Maximum angle of rotation* |
| 90 |
| ° |
Weight*
|
|
8 8 |
|
kg kg |
Dimensions | min. | typ. | max. | unit |
---|---|---|---|---|
Max-50.75-Y L |
–1 |
288 |
+1 |
mm |
Max-50.75-Y-CTM L |
–1 |
288 |
+1 |
mm |
Hollow shaft double square | 16 x 16 |
|
| mm |
Allen key provided for manual adjustment in accordance with these instructions* |
| 4 |
| mm |
Electrical characteristics | min. | typ. | max. | unit |
---|---|---|---|---|
Minimum nominal voltage (at room temperature) | –10 % | 24 | +10 % | VAC/DC |
Maximum nominal voltage (at room temperature) | –10 % | 240 | +10 % | VAC/DC |
Minimum mains frequency | –20 % | 50 | +20 % | Hz |
Maximum mains frequency | –20 % | 60 | +20 % | Hz |
Nominal current (at room temperature) | ||||
Power consumption standby* |
| 5 |
| W |
Power consumption heating mode* |
| 16 |
| W |
Power consumption in operation | ||||
Switch-on peak
|
|
2 2 |
|
A A |
Maximum duty cycle for motor run time* 40 s, 60 s, 90 s, 120 s, 150 s |
100 |
% |
Electrical connection options | |
---|---|
3-point with spring return constant spring return period continuous | Cable type 5+PE, cable diameter 7.5 mm / cable type 6, cable diameter 7.4 mm |
1-wire with spring return with constant spring return period continuous | Cable type 4+PE, cable diameter 7.2 mm / cable type 6, cable diameter 7.4 mm |
Activation CONTROL | min. | typ. | max. | unit |
---|---|---|---|---|
Angle of rotation and position indicator | 95 | ° | ||
Precision electrical* | ~100 | Step | ||
Activation Y | 0 4 | 10 20 | VDC mA | |
Performance data Y and U
|
0 4 0 4 |
|
10 20 10 20 |
VDC mA VDC mA |
Inverting | Setting up wire bridges between terminals 3 and 4 |
Environmental conditions | min. | typ. | max. | unit |
---|---|---|---|---|
Humidity (not condensing) |
|
| 90 | % rH |
Protection class as per DIN EN 60529 | IP67 |
|
|
|
Operation | ||||
| –40 –40 |
| +40 +50 | °C °C |
Storage | ||||
| -40 |
| +70 | °C |
*: Nominal value: please note that nominal values are also subject to tolerances. For more detailed information, see: Note on nominal values