Max-50.75-Y, Max-50.75-Y-CTM

Mechanical properties

min.

typ.

max.

unit

Motor torque (can be configured with rotary switch)*

 

50/75

 

Nm

Motor runtime for 90° (can be configured with rotary switch)*

 

40
60
90
120
150

 

s

Minimum angle of rotation*

 

-5

 

°

Maximum angle of rotation*

 

90

 

°

Weight*

  • Max-50.75-Y
  • Max-50.75-Y-CTM

 

 

8

8

 

 

kg

kg

Dimensions

min.

typ.

max.

unit

Max-50.75-Y

L
W
H

 

–1
–1
–1

 

288
149
116

 

+1
+1
+1

 

mm
mm
mm

Max-50.75-Y-CTM

L
W
H

 

–1
–1
–1

 

288
149
116

 

+1
+1
+1

 

mm
mm
mm

Hollow shaft double square

16 x 16

 

 

mm

Allen key provided for manual adjustment in accordance with these instructions*

 

4

 

mm

Electrical characteristics

min.

typ.

max.

unit

Minimum nominal voltage (at room temperature)

–10 %

24

+10 %

VAC/DC

Maximum nominal voltage (at room temperature)

–10 %

240

+10 %

VAC/DC

Minimum mains frequency

–20 %

50

+20 %

Hz

Maximum mains frequency

–20 %

60

+20 %

Hz

Nominal current (at room temperature)

Nominal current

Power consumption standby*

 

5

 

W

Power consumption heating mode*

 

16

 

W

Power consumption in operation

Nominal current

Switch-on peak

  • at 24 VDC (for approx. 2 seconds)*
  • at 240 VDC (for approx. 2 seconds)*

 

 

2

2

 

 

A

A

Maximum duty cycle for motor run time*

40 s, 60 s, 90 s, 120 s, 150 s

 

100

 

%

Electrical connection options

3-point with spring return constant spring return period continuous

Cable type 5+PE, cable diameter 7.5 mm / cable type 6, cable diameter 7.4 mm

1-wire with spring return with constant spring return period continuous

Cable type 4+PE, cable diameter 7.2 mm / cable type 6, cable diameter 7.4 mm

Activation CONTROL

min.

typ.

max.

unit

Angle of rotation and position indicator

95

°

Precision electrical*

~100

Step

Activation Y

0

4

10

20

VDC

mA

Performance data Y and U

  • Activation YU (for 10 kΩ output impedance)
  • Activation YI (for 100 Ω load / output impedance)
  • Feedback UU (for 10 kΩ…∞ Ω input impedance)
  • Feedback UI (for 0…800 Ω load / input impedance)

 

0

4

0

4

 

 

10

20

10

20

 

VDC

mA

VDC

mA

Inverting

Setting up wire bridges between terminals 3 and 4

Environmental conditions

min.

typ.

max.

unit

Humidity (not condensing)

 

 

90

% rH

Protection class as per DIN EN 60529

IP67

 

 

 

Operation

  • Ambient temperature (T6)
  • Ambient temperature (T5)

–40

–40

 

+40

+50

°C

°C

Storage

  • Ambient temperature

-40

 

+70

°C

*: Nominal value: please note that nominal values are also subject to tolerances. For more detailed information, see: Note on nominal values