Parameter setting

For parameter setting, all rotary drives are equipped with a 10-position switch, a button and a 3-colour LED.

These controls are located on the cable side behind the two small, central blanking plugs or pressure-compensation elements (carefully twist in and out). The blanking plugs need to be removed to operate.

Operation / parameter setting can be undertaken despite pending voltage applied to the rotary drive. Afterwards, the removed blanking plugs must be inserted again to ensure the drive does not lose its IP protection class.

The switch and button are operated using a screwdriver. Never apply force by vigorously pressing and/or twisting as this can cause irreparable damage to the control electronics.

The torque and runtime can also be configured prior to installation. Adjustment of the angle of rotation can only be begun when there is a power supply and the device has been correctly installed.

Rotary switch settings size S

Size S type 5.10 or 15.30 (for types -S, -SF, -BF)

Torque (motor):

5 Nm / 15 Nm

10 Nm / 30 Nm

desired motor run time:

3 s

00

05

15 s

01

06

30 s

02

07

60 s

03

08

120 s

04

09

Remaining size S types (for types -F1, -SF1 and -BF1)

Torque (motor):

8 Nm / 15 Nm

desired motor run time:

3 s

00

15 s

01

30 s

02

60 s

03

120 s

04

Size S type 5.10 or 15.30 (for types -Y, -YF, -CY and -CYF)

Torque (motor):

5 Nm / 15 Nm

10 Nm / 30 Nm

desired motor run time:

7.5 s

00

05

15 s

01

06

30 s

02

07

60 s

03

08

120 s

04

09

Switch position 02 is the factory setting.

Example

ExMax-15.30

Desired parameters:

Torque 30 Nm

Motor run time 30 s/90°

Result:

Switch position 07

Rotary switch settings size M

Type 50.75 for size M

Torque (motor):

50 Nm

75 Nm

desired motor run time:

40 s

00

05

60 s

01

06

90 s

02

07

120 s

03

08

150 s

04

09

Types for size M (-150, -150-S, -60, -60-F, -60-BF, -60-SF)

Torque (motor):

30 Nm / 50 Nm / 60 Nm / 100 Nm / 150 Nm

desired motor run time:

40 s

00

60 s

01

90 s

02

120 s

03

150 s

04

Types for size M (-100, -100-S, -30, -30-F, -50, -50-F, -50-BF, -50-SF)

Torque (motor):

30 Nm / 50 Nm / 60 Nm / 100 Nm / 150 Nm

desired motor run time:

40 s

00

60 s

01

90 s

02

120 s

03

150 s

04

Switch position 02 is the factory setting.

Example

ExMax-50.75

Desired parameters:

Torque 75 Nm

Motor run time 90 s/90°

Result:

Switch position 07